DSC PowerSeries Neo Programming Guide: Every Section 000–999 With Child Settings and Examples

dscpowerseries neoalarmsecurityprogramminginstallersectionskeypadzonespartitions

This is a complete section-by-section reference for the DSC PowerSeries Neo installer programming menu. It covers every major section from 000 through 999, including all child options, toggle bits, valid value ranges, and real-world examples. Written for the HS2016, HS2032, HS2064, and HS2128 panels with firmware v1.x–v3.x.

---

Entering Installer Programming

From an LCD keypad (HS2LCD / HS2LCDRF / HS2LCDWF): Press [*][8][Installer Code] — default installer code is 5555.

From a touchscreen (HS2TCHP / HS2TCHPRO): Tap the gear icon (top right) → enter installer code → tap Installer Programming.

From the main keypad: You must be in the unarmed state. The keypad will display Installer Programming and accept 3-digit section numbers.

Exiting programming: Press [#] repeatedly to back out, or press [*][8][0][0] to exit and save all changes.

> Your installer code: 5555 (change this — see Section 006)

---

How Sections Work

Every section is a 3-digit number (000–999). After entering programming mode, type the section number and press [*] to enter it. Each section then shows either:

Toggle bits are changed by pressing the corresponding zone number key on the keypad. A lit LED = ON (1), unlit = OFF (0). Press [*] to save and advance.

---

SECTIONS 000–009: System / Installer Setup

Section 000 — System Master Reset

Returns the panel to factory defaults. Use with extreme caution. Requires confirmation code entry. All zones, user codes, and partition settings are wiped. Useful on a fresh install before commissioning.

Section 001 — Installer Code

Programs the 4- or 6-digit installer code. The factory default is 5555. Change this on every real installation — 5555 is publicly known.

Section 002 — Master Code

The system master code used by the primary user. Default is typically 1234. Can arm/disarm all partitions and add/delete regular user codes.

Section 003 — DLS / Download Code

4-digit code used by DLS-5 or Connect24 software to remote-program the panel. Change from default. Set to 0000 to disable remote programming.

Section 004 — Shift Code

Used for panel-to-PC communication for DLS. Generally left at factory default unless using remote download.

Section 005 — PC Password

6-digit password for encrypted DLS sessions. Default: 000000. Set to something non-default on live systems.

Section 006 — Installer Code Lock

Toggle bits:

---

SECTIONS 010–099: System Options

Section 010 — System Options Toggle 1

Each bit controls a global system behavior:

BitFunctionDefault
1AC power failure reporting delay (0=30min, 1=no delay)OFF
2Keypad lockout after 5 wrong codes (30 sec)ON
3Audible exit fault (beep on open door at end of exit delay)ON
4Auto-arm on exit if armed stayOFF
5No arm if zone open (prevents arming with open zones)OFF
6Random transmission time (staggers report times)ON
7Tamper reportingON
8Exit delay restart on exit door reopenOFF

Section 011 — System Options Toggle 2

BitFunctionDefault
1PGM output follows ready conditionOFF
2Trouble tone on keypad during alarmON
3Cancel report on disarm after alarmON
4Keypad backlight always onOFF
5Keypad backlight on when armedON
6Squawk when arming (horn chirp)ON
7Squawk when disarmingON
8Siren on during 2-way audioOFF

Section 012 — System Options Toggle 3

BitFunctionDefault
1Fire alarm on silence by code onlyON
2Auto-bypass on second armOFF
3Loss of clock triggers troubleON
4Ground fault monitoringON
5Bell output cut-off time enabledON
6AC fail to panel trouble delay (0=3h wait, 1=report immediately)OFF
7Restore report after alarm when system disarmedON
8Swinger shutdown enabledON

Section 013 — System Options Toggle 4

BitFunctionDefault
1Entry delay alarm on follower zonesOFF
2Auto-arm with no movement on zone (requires PIR zones)OFF
3Real-time clock display on keypadON
4Broadcast message on panel tamperON
5DLS stay armedOFF
6Test transmission enabledON
7Periodic test with zone statusOFF
8Partition enable (multi-partition mode)OFF

> For multi-partition installs: Bit 8 of Section 013 must be ON before Sections 300–320 have any effect.

Section 014 — Bell / Siren Timeout

Number of minutes the bell/siren output runs before auto-cutoff.

Section 015 — AC Failure Reporting Delay

How long the panel waits after AC loss before reporting.

Section 016 — Telephone Ring Detection Count

Number of rings before the panel answers an incoming DLS call.

Section 017 — Swinger Shutdown Count

How many alarms on the same zone before that zone is automatically bypassed until the next disarm.

Section 020 — Entry Delay 1

Entry delay time for zones programmed as Delay 1 type.

Section 021 — Entry Delay 2

Separate entry delay for zones programmed as Delay 2 type. Use when you have secondary entry points that need more time (e.g., a detached garage).

Section 022 — Exit Delay

How long users have to leave after arming before the system is fully active.

Section 023 — Exit Delay for Partition 2

Exit delay specific to partition 2 (if partitions enabled).

Section 024 — Entry Delay 1 for Partition 2

Entry delay for partition 2 Delay-1 zones.

Section 025 — Entry Delay 2 for Partition 2

Entry delay for partition 2 Delay-2 zones.

Section 026–029 — Entry/Exit Delays for Partitions 3–8

Repeated structure as above for partitions 3 through 8.

Section 030 — Communication Delay After Alarm

Seconds the panel waits before calling the monitoring station after an alarm. Gives the user time to disarm a false trigger.

Section 031 — Dialer Attempts

Number of times the panel will retry a failed transmission to the monitoring station.

Section 032 — Test Transmission Time (Hour)

Hour of the day for the daily test transmission (24-hour format, 00–23).

Section 033 — Test Transmission Time (Minute)

Minute of the test transmission (00–59).

Section 034 — Test Transmission Cycle

How often the panel sends a periodic test report.

Section 040 — Zone Expansion Module Assignment

Assigns HSM2108 or similar zone expanders to physical slot addresses on the Corbus.

Section 041 — Keypad Slot Assignments

Maps keypad addresses (set via DIP switches or programming on each keypad) to partition assignments.

Section 042 — PGM Module Assignment

Assigns HSM2208 (8-output PGM modules) to Corbus slot addresses.

Section 050 — Keypad Function Key 1

Assigns a function to the F1 key on the keypad.

Section 051 — Keypad Function Key 2

Same options as Section 050 for the F2 key.

Section 052 — Keypad Function Key 3

F3 key assignment.

Section 053 — Keypad Function Key 4

F4 key assignment.

Section 054 — Keypad Global Options

Toggle bits applied to all keypads on the system:

BitFunction
1Keypad beeps on key press
2Keypad backlight during alarm
3Display "Armed" when armed
4Display zone names on alarm
5Prox tag enabled (HS2LCDRF)
6Tone on trouble condition
7Keypad lockout after failed codes
8Reserved

Section 055 — Door Chime Zones

Select which zones (by zone number) produce a door chime tone on the keypad when opened while disarmed. Press the zone's number key to toggle its chime on/off.

Section 060 — Low Battery Trouble Reporting

Section 061 — Panel Supervision Options

Toggle bits for panel hardware monitoring:

BitFunction
1Monitor AC power failure
2Monitor battery failure
3Monitor bell circuit
4Monitor telephone line
5Monitor auxiliary power supply
6Monitor Corbus communication fault
7Monitor panel tamper
8Monitor ground fault

Section 070 — Wireless Receiver Options

Configures HSM2HOST or integrated wireless receiver behavior:

BitFunction
1Wireless receiver enabled
2Supervision window (0=4h, 1=24h)
3Report wireless supervisory faults
4Jam detection enabled
5Report jam trouble
6RSSI threshold (low=more sensitive)
7Wireless panic reporting
8Wireless key enabled

Section 071 — Wireless Supervisory Window

How long a wireless device can be out of contact before triggering a supervision fault.

Section 072 — Wireless Jam Sensitivity

---

SECTIONS 100–199: Zone Definitions

Sections 100–227 define individual zones. Each 3-digit section corresponds to one zone.

Section mapping:

Each Zone Section Contains These Child Options:

Child Section 1: Zone Type Navigate to [zone section][*][1] to set the zone type:

CodeZone TypeDescription
00DisabledZone ignored completely
01Delay 1Uses Entry Delay 1 timer — main entry door
02Delay 2Uses Entry Delay 2 timer — secondary entry
03Instant PerimeterTriggers alarm immediately when armed away; bypassed when armed stay
04Interior Stay/AwayActive when armed away only; bypassed when armed stay
05Interior FollowFollows delay zones — alarm only if delay expires
0624-Hour SilentAlways active, no siren, reports silently to monitoring
0724-Hour AudibleAlways active, triggers full alarm with siren
0824-Hour AuxiliaryAlways active, activates auxiliary output only
09Momentary PanicReports alarm but produces no bell output
10Fire (standard)Triggers fire alarm, activates fire output
11Smoke (bi-directional)Supports remote reset via PGM; standard for smoke detectors
12Fire (latching)Like type 10, but requires keypad reset
13GasReports gas alarm, activates gas output
14Flood / WaterReports water alarm
15Carbon MonoxideCO alarm type
16Medical / Pendant24-hour, reports to medical channel
17Freeze / TemperatureTemperature trigger alarm
19Keyswitch MomentaryTap key switch to toggle arm/disarm
20Keyswitch MaintainedArmed when switch closed, disarmed when open
21Keyswitch ToggleEach closure toggles arm state
22PGM InputUsed to trigger a PGM output, not an alarm zone
23No Alarm ResponseLogs and reports event, no siren or alarm output
25Audible PanicImmediate full alarm — panic button
26Silent PanicReports to monitoring only, no local alarm
27SupervisoryUsed for auxiliary equipment supervision

Real-world zone type examples for a residential install:

Child Section 2: Partition Assignment Which partition(s) this zone belongs to. Press bit keys 1–8 for partitions 1–8.

Child Section 3: Report Codes Two-digit hex codes sent to the monitoring station for alarm and restore events on this zone. Usually pre-configured by the monitoring provider.

Child Section 4: Zone Attributes 8-toggle bits controlling this zone's behavior:

BitFunction
1Zone bypass enabled (user can bypass)
2Alarm memory (zone stays in alarm list after restore)
3Chime (door chime when opened while disarmed)
4Trouble = alarm (zone trouble counts as alarm, not just trouble)
5Swinger shutdown enabled on this zone
6Force arm enabled (arm while zone is open, zone auto-bypassed)
7Alarm transmission delay applies to this zone
8Transmit zone restore

Child Section 5: Zone Name Select from the panel's built-in name list or enter a custom name.

Child Section 6: Zone Type Details / Wireless Settings For wireless zones (enrolled via HSM2HOST):

Example: Programming Zone 1 as a Front Door

  1. Enter programming: [*][8][5555]
  2. Enter zone section: [1][0][1][*]
  3. Child section 1 (zone type): [1][*] → type 01[*] (Delay 1)
  4. Child section 2 (partition): [2][*] → press [1] to enable partition 1 → [*]
  5. Child section 4 (attributes): [4][*] → enable bits 1,2,3,5,8 → [*]
  6. Child section 5 (name): [5][*] → scroll to "Front Door" → [*]
  7. Press [#] to return

Example: Programming Zone 5 as a Smoke Detector

  1. [*][8][5555][1][0][5][*]
  2. Type: [1][*]11[*] (Smoke bi-directional)
  3. Partition: [2][*] → bit 1 → [*]
  4. Attributes: [4][*] → enable bits 2,8 (alarm memory + restore) → [*]
  5. Name: [5][*] → "Smoke Detector" or "Living Room Smoke"

---

SECTIONS 200–299: User Codes

Section 200 — System Master Code

The highest-privilege user code (excluding installer). Can add/delete users, change options, and access all partitions. Default: 1234. Change on every install.

Section 201–240 — User Codes 1–40

Each section programs one numbered user code.

User code child options:

BitFunction
1Can arm system
2Can disarm system
3Can bypass zones
4Can add/delete users (supervisory)
5Can access door access control
6Duress code (triggers silent panic when used)
7Code is temporary (one-time use)
8Remote arm/disarm via telephone

Section 250 — User Code Length

Section 251 — Duress Code Options

Configures what happens when a duress code is entered:

---

SECTIONS 300–399: Partition Options

> Requires partition mode enabled (Section 013, Bit 8 = ON)

Section 300 — Partition Options Toggle 1

BitFunction
1Partition 1 enabled
2Partition 2 enabled
3Partition 3 enabled
4Partition 4 enabled
5Partition 5 enabled
6Partition 6 enabled
7Partition 7 enabled
8Partition 8 enabled

Section 301 — Partition Common Zone Assignments

Zones assigned here are active on ALL partitions simultaneously. Useful for fire zones, panic buttons, and common area sensors.

Section 310–317 — Entry Delay 1 for Partitions 1–8

Individual entry delay 1 setting per partition (overrides global Section 020 for that partition).

Section 320–327 — Exit Delay for Partitions 1–8

Individual exit delay per partition.

Section 330–337 — Partition Arm/Disarm Options

For each partition, toggle bits control:

BitFunction
1Auto-arm enabled for this partition
2Auto-disarm enabled
3Arm stays enabled (away-to-stay downgrade allowed)
4Disarm after alarm requires master code
5Forced arm enabled (arm with open zones bypassed)
6Quick arm enabled (no code needed to arm)
7Stay/Away arm available
8Night arm available

Section 350 — Partition 1 Auto-Arm Time

24-hour clock time for automatic arming of partition 1.

Section 351–357 — Auto-Arm Times for Partitions 2–8

Section 360 — Partition 1 Auto-Disarm Time

Format: HHMM

Section 361–367 — Auto-Disarm Times for Partitions 2–8

---

SECTIONS 400–499: Communication / Reporting

Section 400 — Communication Options Toggle 1

BitFunction
1Dialer enabled
2Use PSTN phone line
3Use IP/GSM communicator (HSM2HOST / TL280)
4Backup IP if PSTN fails
5Report opening/closing events
6Report bypass events
7Report zone trouble events
8Report test transmissions

Section 401 — Communication Options Toggle 2

BitFunction
1Report AC failure
2Report battery failure
3Report bell trouble
4Report telephone line fault
5Report panel tamper
6Report wireless supervisory
7Report Corbus faults
8Report all zones or only alarmed zones

Section 410 — Central Station Phone Number 1

Up to 16 digits. Enter digits of the monitoring station's telephone number. Use [*] to insert a pause where needed (analog dialing).

Section 411 — Central Station Phone Number 2

Backup monitoring phone number for redundancy.

Section 412 — Account Number

4- or 6-digit account code assigned by the monitoring station. This identifies your account in their system. Usually provided by the monitoring company.

Section 413 — Account Number for Partition 2

Separate monitoring account code for partition 2 (if reporting separately).

Section 420 — Communication Format

> Use Contact ID (00) for all modern installs.

Section 430 — IP Communicator Options (TL280 / TL265 / HSM2HOST)

Configuration for network-connected communicator module:

BitFunction
1IP reporting enabled
2Receiver 1 IP address is primary
3Swap receivers on failure
4DHCP enabled (auto IP assignment)
5Poll primary receiver every 30 seconds
6Poll secondary receiver
7Trouble if no ACK from receiver
8Report IP communicator trouble

Section 431 — IP Receiver 1 Address

Enter the IPv4 address of the primary IP receiver at the monitoring station.

Section 432 — IP Receiver 2 Address (Backup)

Section 433 — IP Receiver Port Number

Port number for the IP receiver (typically 2101 for Sur-Gard / Alarm Receiving Centre software).

Section 440 — Cellular / GSM Options

For TL2603G / 3G or LTE communicator modules:

BitFunction
1Cellular primary reporting
2Cellular backup to IP
3Roaming enabled
4Report cellular signal strength
5Trouble if signal lost >30 minutes

Section 450 — Report Codes: Zone Alarms

Zone alarm Contact ID codes. Each zone pair occupies one section.

Section 460 — Report Codes: Zone Restores

Section 470 — Report Codes: Openings (Arm Away)

Contact ID code sent when partition is armed away.

Section 471 — Report Codes: Closings (Disarm)

Contact ID code for disarm events.

Section 472 — Report Codes: Armed Stay

---

SECTIONS 500–599: PGM Output Programming

The PowerSeries Neo supports PGM (programmable output) modules via HSM2208 (8 outputs) on the Corbus.

Section 500 — PGM Output 1 Options

Each PGM output section configures one relay or transistor output.

Child Section 1: Output Type

CodeOutput Behavior
00Disabled
01Steady (on = on, off = off)
02Pulse (1-second pulse then off)
03Follow bell output
04Follow system armed (on when armed)
05Follow system disarmed (on when disarmed)
06Alarm output (on during any alarm)
07Fire alarm output
08Smoke detector reset (brief power cycle)
092-way audio (activates speaker circuit)
10Keyswitch output (follows keyswitch zone)
11Door strike (follow zone, timed)
12Follow zone (output mirrors zone state)
13Strobe (follows alarm with flash pattern)
14Trouble output (on when any trouble exists)
15AC failure output
16System ready output (on when ready to arm)
17Entry delay output (on during entry delay)
18Exit delay output (on during exit delay)
19Partition armed output

Child Section 2: Activation Event Which zone or system event triggers this output (for output types that follow a zone/event).

Child Section 3: Pulse/On Time How long the output stays active (for pulse outputs):

Child Section 4: Output Attributes

BitFunction
1Output inverted (normally on, off on event)
2Follow only alarm, not trouble
3Bypass when zone bypassed
4Output active on restore

Sections 501–516 — PGM Outputs 2–16

Same structure as Section 500, repeated for each output.

Real-world PGM examples:

Exterior siren: Output type 03 (follow bell), wired to bell input of external speaker.

Smoke detector reset circuit: Output type 08, set to pulse 5 seconds — brief power interruption resets 2-wire smoke detectors after alarm.

Gate/door strike: Output type 11 (door strike, timed), pulse time = 5 seconds (open briefly when valid code entered).

"System armed" LED: Output type 04 (follow armed), drives an LED indicator by the main entrance.

---

SECTIONS 600–699: Access Control / Elevator

Section 600 — Access Control Module Options

For HSM2204 door access control modules on the Corbus.

Section 601 — Door 1 Access Options

BitFunction
1Door access enabled
2Require code + prox tag (dual factor)
3Door forced open alarm
4Door held open alarm
5Rex (request to exit) zone enabled
6Lock on alarm
7Unlock on fire alarm
8Auto-lock enabled

Section 602 — Door 1 Strike Type

Section 610 — Door Hold-Open Time

How long the door strike stays unlocked after a valid access:

Section 620 — Door Forced Open Alarm Delay

Time door can be open before "door forced" alarm triggers:

Section 630 — Sections 601–616: Doors 2–16

Same structure repeats for each additional access-controlled door.

---

SECTIONS 700–799: Wireless Device Enrollment

Section 700 — HSM2HOST Wireless Receiver

Enter the serial number or use auto-enrollment to register devices.

Section 701 — Wireless Zone Enrollment Mode

Enrolling a Wireless Device (Auto Mode):

  1. Enter programming: [*][8][5555]
  2. Go to Section 701 → select zone number → select auto-enroll
  3. Trigger the device (open door sensor, walk in front of PIR, press panic button)
  4. Panel acknowledges serial number and assigns to zone
  5. Program zone type and attributes via Sections 100–199

Section 710 — Wireless Prox Tag Enrollment

Tags used for keypad proximity arming (HS2LCDRF):

  1. Section 710 → select user number
  2. Present tag to keypad reader
  3. Tag serial number is registered

Section 720 — Wireless Key (Keyfob) Enrollment

Arm/disarm keyfobs:

  1. Section 720 → select keyfob slot (1–32)
  2. Press any button on keyfob
  3. Assign arm, disarm, and panic button functions
  4. Section 721 sets keyfob button behavior (each button 1–4 assignable)

Section 730 — Wireless Repeater Enrollment

For HSM2HOST or WT5500 repeaters extending wireless range in large buildings.

---

SECTIONS 800–899: Telephone / DLS Options

Section 800 — Telephone Line Options

BitFunction
1Telephone line monitoring enabled
2Single-line detection (double reporting suppressed)
3Detect cut telephone line
4Report line fault to monitoring
5DNIS format transmission
6Expanded format (more digits in report)
7TDD compatibility mode
8Wait for dial tone before dialing

Section 801 — Dial Tone Detection Pause

Seconds to wait for dial tone before aborting a call:

Section 802 — Time Between Dial Attempts

How long to wait between retry calls to monitoring:

Section 810 — DLS Incoming Call Window

Hours the panel will accept incoming DLS calls after a trigger event:

Section 811 — DLS Options

BitFunction
1DLS enabled
2Installer code required for DLS session
3Allow DLS to change installer code
4Allow DLS to reset factory defaults
5DLS can arm/disarm system
6Call back enabled (panel calls DLS back)
7Encrypted DLS session
8DLS connection requires panel to initiate

Section 820 — DLS Callback Number

Phone number the panel calls back for DLS verification. Only used if Section 811, Bit 6 is ON.

---

SECTIONS 900–999: Clock, Maintenance & Diagnostics

Section 900 — Current Time

Set the panel's real-time clock.

Section 901 — Current Date

Section 902 — Clock Options

BitFunction
112/24 hour display (0=12h, 1=24h)
2Automatic DST adjustment
3DST adjustment +1 hour in spring
4NTP time sync (if IP communicator present)

Section 910 — System Event Log (View Mode)

Scroll through the panel's event buffer (last 500 events):

Section 911 — Event Log Options

BitFunction
1Log zone alarms
2Log zone restores
3Log arm/disarm events
4Log bypass events
5Log trouble events
6Log access control events
7Log system events
8Log DLS access

Section 920 — Panel Reset / Test Options

Section 930 — Diagnostic Mode

Real-time Corbus module status:

Section 940 — Module Firmware Versions

View the firmware version running on each connected module. Navigate by module address.

Section 950 — Panel Self-Test

Runs an internal diagnostics check:

  1. Tests all onboard zone inputs
  2. Tests bell output
  3. Tests PGM outputs
  4. Tests Corbus communication to each module
  5. Results displayed on keypad

Section 960 — Bell / Siren Test Output

Triggers the bell output for 2 seconds for test purposes. Warn occupants before running.

Section 970 — Zone Resistance Test

Displays the measured resistance on each hardwired zone terminal:

Section 980 — Communication Test

Forces an immediate test transmission to the monitoring station. The monitoring station should acknowledge within 30–90 seconds.

Section 990 — Corbus Module Status

Lists all modules detected on the Corbus (4-wire bus):

Section 991 — Corbus Wiring Diagnostics

Voltage and current readings on the Corbus terminals:

Section 999 — Factory Default Reset

Wipes everything — all zones, codes, communication settings, module assignments. Use only on fresh installs or when panel must be completely recommissioned.

---

Quick Reference: Common Programming Sequences

Initial Site Setup Checklist

  1. Section 001 — Change installer code from 5555
  2. Section 200 — Change master user code from 1234
  3. Section 413 — Enter monitoring account number
  4. Section 410 — Enter monitoring phone/IP
  5. Section 022 — Set exit delay (recommend 60–90 seconds)
  6. Section 020 — Set entry delay (recommend 30–45 seconds)
  7. Section 014 — Set bell timeout (recommend 4–8 minutes)
  8. Sections 101–1NN — Program all zones with type, partition, attributes
  9. Section 980 — Send test transmission to verify monitoring
  10. Section 910 — Review event log and confirm clean state

Adding a New User Code

  1. [*][8][Installer Code] to enter programming
  2. Navigate to Section 201–240 for the desired user slot
  3. Enter 4-digit or 6-digit code → [*]
  4. Set partition access and attributes in child sections
  5. [#] to exit

Enrolling a New Wireless Zone

  1. [*][8][Installer Code]
  2. Section 701 → select zone number → auto-enroll
  3. Trigger device → confirm serial
  4. Section 101-1NN → set zone type, partition, attributes
  5. Section 055 → add to door chime if desired

Resetting a Smoke Detector After Alarm

If smoke detectors use a PGM reset circuit (Output type 08):

  1. Disarm system (clears alarm memory)
  2. Locate smoke reset PGM output
  3. Panel auto-pulses for 5 seconds on disarm if programmed
  4. Or manually: [*][7][2][2] from keypad to activate reset output

Checking Corbus Module Status (9 expansion modules)

  1. [*][8][5555]
  2. Section 990
  3. Scroll through addresses 1–9
  4. Each shows: type, firmware, status
  5. Address with fault shows COMM FAIL — check wiring at that module

---

Keypad Status Light Reference

During normal operation, the keypad's zone LEDs and indicators mean:

IndicatorMeaning
Zones 1–8 litThose zones are open
READY light onAll zones closed, system ready to arm
ARMED light onSystem is armed
TROUBLE light onSystem has a trouble condition — press [*][2] to view
AC indicator offAC power lost, running on battery
DC indicator offBattery low or missing
Flashing TROUBLETamper or module communication fault

Viewing trouble conditions: Press [*][2] from the keypad to see a numbered list of active troubles.

---

*Installer code for this installation: 5555 (change immediately if live system). Programming manual reference: DSC PowerSeries Neo HS2016/HS2032/HS2064/HS2128 Installer Programming Guide v3.x.*